As reported by CISA in advisory ICSA-26-258-03, mySCADA Technologies has disclosed two critical vulnerabilities in myPRO Manager affecting versions 2.1 and earlier. These are not subtle logic bugs — they are fundamental authentication failures in an OT management product deployed across critical infrastructure sectors worldwide.
Vulnerability Summary
| CVE | CVSS v3.1 | Flaw | Impact |
|---|---|---|---|
| CVE-2026-73807 | 9.8 Critical | Missing Authorization on command API | Unauthenticated access to privileged management functions |
| CVE-2026-82567 | Not specified (High/Critical expected) | Missing Authentication on SMS gateway endpoint | Arbitrary SMS sending via connected GSM modem |
Affected product: mySCADA myPRO Manager <= 2.1Patch available: Version 2.2 (vendor recommends immediate update)Active exploitation: Not confirmed in the wild at time of advisoryAffected sectors: Critical Manufacturing, Energy, Food and Agriculture, Transportation, Water and Wastewater
Why This Matters
The first vulnerability is the headline issue. A CVSS 9.8 missing-authorization flaw on a command API means anyone with network reachability to the management interface can invoke privileged functions without credentials. In OT environments, management APIs often control SCADA project deployment, device communication tunnels, and system configuration. An unauthenticated attacker gaining that level of control could manipulate operational processes, push malicious configurations, or establish persistence within the OT network.
The second flaw — an unauthenticated SMS gateway — may seem lower stakes, but it is a meaningful operational risk. Attackers could abuse the connected GSM modem for smishing campaigns using the organization's sender identity, drain prepaid SMS credits, or use the channel as a covert exfiltration path. In environments where GSM modems serve as out-of-band alerting for critical alarms, flooding the modem could also degrade or disrupt legitimate alerting.
The pattern here is familiar: an OT product exposing privileged APIs without authentication, deployed in environments where segmentation is often inadequate. These are exactly the flaws threat actors look for when pivoting from IT to OT.
Who Is Most Exposed
Shield53 Recommendations
Immediate Actions
- Patch to Version 2.2 now. If internet-connected, the manager should auto-notify; otherwise download directly from mySCADA's portal. Validate the update in a test environment first if operational constraints require it, but do not delay beyond a reasonable validation window.
- Restrict network access to the myPRO Manager command API. Apply host-based firewalls or ACLs limiting access to the management interface to a defined jump host or administrator workstation subnet only.
- Isolate the GSM notification gateway. Ensure the HTTP endpoint for SMS sending is not reachable from user networks. If SMS alerting is not in use, disable the gateway entirely.
- Hunt for exposure. Inventory all mySCADA deployments across the organization — distributed OT sites are often untracked. Identify any instance running version 2.1 or earlier and prioritize patching by criticality of the site.
- Deploy network monitoring for the command API port. Alert on any access from non-administrator source IPs. Post-patch, this remains good hygiene for detecting misconfiguration or future issues.
Broader Hardening
OT product authentication failures remain endemic. Defenders should treat every management API in their OT environment as untrusted until independently verified. Where vendors offer no authentication or only weak authentication on management functions, network-layer isolation becomes the primary compensating control. This advisory is a reminder that the responsibility for OT security often falls on the operator, not the vendor.